Water reducers in pressed air systems
Water by compressed air is a common issue, therefore are the most compressed air systems suited with water reducers- Also important is the fact that air condensing in the lines to the air supply points by movement, temperature and external temperature changes. We like to point the attention on a products line of water reducers , which can be installed at the points of your problem area. you can always consult us.
Applications: The most places of attention in your Air supply system and the solutions to improve.
To eliminate water and dirt direct in the main supply line behind the Compressor or at a high volume air supply point – the Eliminex can be used – in the case of oil free air the Eliminex combo can be used. Key is high volume.
Depending on the model the max volume flow is 8827 Nm3/hr
Main air supply line or air supply point : For the elimination of dirt, water and oil a Eliminizer Combo can be installed . Eliminizer combo are installed direct behind the compressor or at a air supply point which is used at high volume air supply point. Note : Eliminizer used a very effective technique to eliminate the water from the air – more information in purification of air below.
At air supply point : By elimination of dirt and water direct behind the compressor of at air supply point to max 93 m3/ hour
At air Supply point; elimination of dirt and water. Highly effective reducerend of water due a combination of water reducing techniques in one item. In case of oil free air at this supply point the Eliminizer combo can be installed.
For very critical air supply point, which require very clean , oil free with dew point suppressed air the eliminator II can be used.
Air purification with the Duncan Rogers eliminizer air dryers
4 air drying principes in one device
In the first phase we find a combination lowing the speed, due to the volume increase. At the same moment a centrifugal spin will be created in the air flow . The combination of reducing speed followed by the centrifugal spin will let a effective reducing of water in the supply air
By re-route the air flow 180 degrees towards the filter the air flow will reducing even more water.
By leading the air flow trough a filter, which enlarge the still captured water droplets and the gravity will separate the from the enlarged water droplets
After the Filter the air flow will be captured in high speed spin and the so-called dry phase will force out last water remains – the finale step is a filter of combined elements for cleaning.
Produces clean dry air at the supply point.
Installation not more than 5 meter of the air supply point.
Volume flow: Till 240 Nm3/hr
Pressure drop: max 0,35 bar
Suited with drain
Connection: from 1/4 inch till 1 inch BSPP ( British Standard Parallel Pipe) Housing : Poly carbonate , Epoxy coated steel and RVS
Eliminizer with polycarbonate housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max volume flow Nm3/hr | Max operaton pressure bar | Max. operation temperature °C |
3P-020-PP2-F | 16 | 32 | 10,5 | 50 |
3P-035-PP2-F | 27 | 56 | 10,5 | 50 |
3P-035-PP3-F | 27 | 56 | 10,5 | 50 |
3P-035-PP4-F | 27 | 56 | 10,5 | 50 |
3P-060-PP4-F | 48 | 96 | 10,5 | 50 |
3P-090-PP6-F | 72 | 115 | 10,5 | 50 |
3P-150-PP8-F | 120 | 240 | 10,5 | 50 |
steel housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max volume flow Nm3/hr | Max operaton pressure bar | Max. operation temperature °C |
3P-020-MP2-F | 16 | 32 | 14 | 80 |
3P-035-MP4-F | 27 | 56 | 10,5 | 80 |
3P-060-MP4-F | 48 | 96 | 10,5 | 80 |
3P-090-MP6-F | 72 | 144 | 10,5 | 80 |
3P-090-MP8-F | 120 | 240 | 14 | 80 |
RVS 316 housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max volume flow Nm3/hr | Max operaton pressure bar | Max. operation temperature °C |
3P-060-SP4-F | 48 | 96 | 10,5 | 50 |
Tab Content
Dimensions housing
Dimension polycarbonate housing | |||||
Model number | connection Inch BSPP | weight Kg | h mm | w mm | D mm |
3P-020-PP2-F | 1/4 | 0.9 | 190 | 76 | 66 |
3P-035-PP2-F | 1/4 | 2,3 | 292 | 95 | 95 |
3P-035-PP3-F | 3/8 | 2,3 | 292 | 95 | 95 |
3P-035-PP4-F | 1/2 | 2,3 | 292 | 95 | 95 |
3P-060-PP4-F | 1/2 | 2,3 | 292 | 95 | 95 |
3P-090-PP6-F | 3/4 | 3,2 | 393 | 127 | 127 |
3P-150-PP8-F | 1 | 3,2 | 393 | 127 | 127 |
Eliminizer Steel housing | |||||
Model number | connection Inch BSPP | weight Kg | h mm | w mm | D mm |
3P-020-MP2-F | 1/4 | 0,9 | 190 | 76 | 66 |
3P-035-MP4-F | 1/2 | 1,8 | 292 | 95 | 95 |
3P-060-MP4-F | 1/2 | 1,8 | 292 | 95 | 95 |
3P-090-MP6-F | 3/4 | 3,2 | 393 | 127 | 127 |
3P-090-MP8-F | 1 | 3,2 | 393 | 127 | 127 |
Eliminizer met RVS316 behuizing | |||||
Model number | connection Inch BSPP | weight Kg | h mm | w mm | D mm |
3P-060-SP4-F | 1/2 | 1,7 | 283 | 83 | 83 |
Eliminizer combo Details
Technical details
Produces clean dry and oil fee air at the supply point.
Installation not more than 5 meter of the air supply point.
Volume flow: Till 240 Nm3/hr
Pressure drop: max 0,5 bar
Suited with drain
Connection: from 1/4 inch till 1 inch BSPP ( British Standard Parallel Pipe) Housing : Poly carbonate , Epoxy coated steel and RVS
Eliminizer combo polycarbonate housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max operation pressure bar | Max. operation temperature °C |
3P-020-PP2-DC | 16 | 21 | 10,5 | 50 |
3P-060-PP2-DC | 48 | 96 | 10,5 | 50 |
3P-060-PP3-DC | 48 | 96 | 10,5 | 50 |
3P-060-PP4-DC | 48 | 96 | 10,5 | 50 |
3P-090-PP6-DC | 72 | 120 | 10,5 | 50 |
3P-150-PP8-DC | 120 | 240 | 10,5 | 50 |
Eliminizer combo steel housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max operation pressure bar | Max. operation temperature °C |
3P-020-MP2-DC | 16 | 32 | 14 | 80 |
3P-060-MP4-DC | 48 | 96 | 10,5 | 80 |
3P-090-MP6-DC | 72 | 144 | 10,5 | 80 |
3P-150-MP8-DC | 120 | 240 | 14 | 80 |
Eliminizer RVS 316 housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max operation pressure bar | Max. operation temperature °C |
3P-060-SP4-DC | 48 | 96 | 10,5 | 50 |
Dimensions housing
Eliminizer combo polycarbonate housing | |||||
Model number | Connection Inch BSPP | Weight Kg | h mm | w mm | D mm |
3P-020-PP2-DC | ¼ | 2,7 | 190 | 170 | 66 |
3P-060-PP2-DC | ¼ | 3,6 | 292 | 210 | 95 |
3P-060-PP3-DC | 3/8 | 3,6 | 292 | 210 | 95 |
3P-060-PP4-DC | ½ | 3,6 | 292 | 210 | 95 |
3P-090-PP6-DC | ¾ | 6,3 | 393 | 275 | 127 |
3P-150-PP8-DC | 1 | 6,3 | 393 | 275 | 127 |
Eliminizer combo Steel housing | |||||||
Model number | Connection Inch BSPP | Weight Kg | h mm | w mm | D mm | ||
3P-020-MP2-DC | 1/4 | 2,2 | 190 | 170 | 66 | ||
3P-060-MP4-DC | 1/2 | 4 | 292 | 210 | 95 | ||
3P-090-MP6-DC | 3/4 | 6,8 | 393 | 275 | 127 | ||
3P-150-MP8-DC | 1 | 6,8 | 393 | 275 | 127 |
Eliminizer combo RVS316 housing | |||||
Model number | Connection Inch BSPP | Weight Kg | h mm | w mm | D mm |
3P-060-SP4-DC | 1/2 | 3,8 | 283 | 178 | 83 |
The eliminator II is a absorption dryer designed for intermittent low volume flow from 11 till 16 Nm3/hr. Only in Steel housing available.
The first stage water reduction followed by an active coal oil separator afterwards an active aluminum for dew point suppression to – 40°C
Produced clean, dry, oil free air for critical applications.
The recommended way for installation is max. 5 meter from the air supply point.
Connection are ½ inch BSPP (British Standard parallel pipe).
Max. pressure drop is 0.5 bar.
A automatic drain valve is standard mounted
Eliminator II with steel housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max. operation pressure bar | Max. operation temperature °C |
E4000 with pressure regular | 11 | 16 | 10,5 | 40 |
N4000 without Pressure regular | 11 | 16 | 10,5 | 40 |
Eliminator with steel housing | |||||
Model number | Connection Inch BSPP | Weight Kg | H mm | wide mm | D mm |
E4000 with pressure regular | 1/2 | 5,8 | 483 | 432 | 120 |
N4000 without pressure regular | 1/2 | 5,5 | 483 | 356 | 120 |
The Eleminex eliminate water and dirt from 3 micron from the main air supply line.
The pressure drop is only 0,06 bar.
The connection are from 3/4 inch till 2 inch BSPP (British Standard parallel pipe) and flange connections from 3 inch till 6 inch.
The housing is in two variants: Aluminium and epoxy coated steel.
The max. volume flow is 8827 Nm3/hr
an Automatic drain valve is standard installed.
Eliminex Aluminium housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max. operation pressure bar | Max. operation temperature °C |
IP-120-MP6-F | 96 | 193 | 14 | 80 |
IP-175-MP8-F | 140 | 280 | 14 | 80 |
IM-300-P12-F | 240 | 481 | 14 | 80 |
IM-300-P16-F | 240 | 481 | 14 | 80 |
IM-400-P12-F | 321 | 642 | 14 | 80 |
IM-700-P16-F | 562 | 1124 | 14 | 80 |
Eliminex steel housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max. operation pressure bar | Max. operation temperature °C |
IM-2500-MFDX | 2006 | 4012 | 10,5 | 50 |
IM-2500-MFEX | 2006 | 4012 | 10,5 | 50 |
IM-2500-MFFX | 8827 | 8827 | 10,5 | 50 |
Eliminex Aluminium housing | |||||
Model number | Connection Inch BSPP | Weight Kg | H mm | W mm | D mm |
IP-120-MP6-F | ¾ | 3,2 | 394 | 127 | 127 |
IP-175-MP8-F | 1 | 3,2 | 394 | 127 | 127 |
IM-300-P12-F | 1 1/2 | 13,2 | 686 | 198 | 198 |
IM-300-P16-F | 2 | 13,2 | 686 | 198 | 198 |
IM-400-P12-F | 1 1/2 | 16,8 | 762 | 216 | 216 |
IM-700-P16-F | 2 | 16,8 | 762 | 216 | 216 |
Eliminex steel housing | |||||
Model number | Connection Flange inch | Weight Kg | H mm | W mm | D mm |
IM-2500-MFDX | 3 | 113,4 | 1219 | 464 | 407 |
IM-2500-MFEX | 4 | 120,2 | 1219 | 518 | 407 |
IM-2500-MFFX | 6 | 163,3 | 1524 | 594 | 407 |
The Eleminex combo is combination of Eliminex and coalescing filter, a two-stage system.
Eliminate water, oil and dirt bigger than 0.01 micron from the main air supply line.
The pressure drop is only 0,14 bar.
Connections: from 3/4 inch till 2 inch BSPP (British Standard parallel pipe).
The housing is Aluminium.
The max. volume flow is 1124 Nm3/hr
Standard is an automatic drain valve installed.
Eliminex Combo Aluminium Housing | ||||
Model number | Optimal Volume flow Nm3/hr | Max. volume flow Nm3/hr | Max. operation pressure bar | Max. operation temperature °C |
IP-090-MP6-DC | 72 | 114 | 14 | 80 |
IP-150-MP8-DC | 120 | 240 | 14 | 80 |
IM-300-P12-DC | 240 | 481 | 14 | 80 |
IM-300-P16-DC | 240 | 481 | 14 | 80 |
IM-400-P12-DC | 321 | 642 | 14 | 80 |
IM-700-P16-DC | 562 | 1124 | 14 | 80 |
Eliminex Combo aluminium housing | |||||
Model number | Connection Inch BSPP | weight Kg | H mm | W mm | D mm |
IP-090-MP6-DC | ¾ | 6,8 | 482 | 154 | 117 |
IP-150-MP8-DC | 1 | 6,8 | 482 | 254 | 117 |
IM-300-P12-DC | 1 1/2 | 26,2 | 686 | 419 | 198 |
IM-300-P16-DC | 2 | 26,2 | 686 | 419 | 198 |
IM-400-P12-DC | 1 1/2 | 32,7 | 863 | 482 | 216 |
IM-700-P16-DC | 2 | 33,6 | 863 | 482 | 216 |
The Stealth is a filter –dryer and works at a identical principle as the de Eliminizer. The Stealth is available with and with pressure regulator.
Produces clean, dry air for critical applications at the air supply point.
Recommended is to install the Stealth within max. 5 meters from the air supply point.
The aluminum housing has a connection of 1/2 inch BSPP (British Standard Parallel Pipe).
The Stealth is suitable till volume flows of 96 m3/hour.
The max. pressure drop is 0.35 bar. Standard is a manual operated drain valve installed .
Stealth aluminium housing | ||||
Model number | Optimal volume flow m3/hour | Max. volume flow m3/hour | Max. operation pressure in bar | Max. operation temperature. in °C |
STLH-6900 without pressure regulator | 48 | 96 | 14 | 80 |
STLH-6950-PB with pressure regulator | 48 | 96 | 14 | 80 |
Stealth aluminium housing | |||||
Model number | Connection inch BSPP | weight kg | H mm | W mm | D mm |
STLH-6900 without pressure regulator | 1/2 | 1,8 | 292 | 95 | 95 |